ProTech‐GII

The ProTech-GII is a safety device designed for overspeed protection, capable of safely shutting down steam, gas, and hydroelectric turbines of all sizes when overspeed or overacceleration is detected.

Product description and features

This device accurately monitors turbine rotor speed and acceleration via active or passive MPUs (magnetic sensors) and issues a stop command to the turbine’s trip valves or the corresponding trip system.

Depending on the system design, the ProTech-GII can be purchased with two dual-redundant trip relay outputs using 2-out-of-3 voting architecture, or with three independent non-voted trip relay outputs. Individual alarm relays, 4-20 mA speed displays, and Modbus® communications facilitate its integration into any turbine safety system.

* — Modbus is a trademark of Schneider Automation Inc.

The ProTech-GII is available in flush-mount models for installation inside the front door of a standard 24″ (610 mm) cabinet or in wall-mounted models near the turbine skid. Designed for harsh environments when installed in an enclosure, the device has an IP56 rating (dust-protected and fully protected against strong water jets).

Built for high reliability, each ProTech-GII module (A, B, C) accepts two high-voltage power inputs (90-240 Vac / 100-150 Vdc) or one high-voltage power input (90-240 Vac / 100-150 Vdc) and one low-voltage input (18-32 Vdc). This design operates on high signal selection, allowing the device to function fully with either or both power sources.

Certified IEC61508 SIL-3
Compliant with API670 and API612 standards
2-out-of-3 voting
High availability (TMR)
Acceleration protection
Online testing
Online repair
Overspeed trip and test logs
Modbus communications
Password protection
12-millisecond response time (independent voting output models)
Internal frequency generator
Optional Ethernet communication gateway